,缺水地區(qū)可延長(zhǎng)至96h。
the fire water pool of the time, should not be more than 48h, water shortage area can be extended to 96h.
(4)消防水池的儲(chǔ)備量包括室外消防用水量時(shí)
,其水池應(yīng)符合有關(guān)要求
。
the amount of water in the fire pool, including the amount of water used for outdoor fire protection, shall be in accordance with the relevant requirements.
(5)消防水池設(shè)計(jì)應(yīng)池內(nèi)水經(jīng)常流動(dòng),以防腐化變質(zhì)
。
the design of fire water tank water should ensure that often flow, to prevent corruption.
(6)寒冷地區(qū)的消防水池應(yīng)有防凍設(shè)施口在儲(chǔ)罐區(qū)應(yīng)有易燃
,可燃液體不流入消防水池的設(shè)施。
the fire pool in the cold area should be anti freezing facilities in the storage tank area should be guaranteed to be flammable, flammable liquid does not flow into the fire pool facilities.
結(jié)論與建議
Conclusion and suggestion
(1)建議三本規(guī)范對(duì)高位消防水箱儲(chǔ)水量和設(shè)置高度采用同一原則
,即消防水箱應(yīng)滿足火災(zāi)初期供水不利樓層和部位消防水壓和水量的要求
。
it is recommended that the three specifications of the high fire tank water storage and setting height of the same principle, that is, the fire tank should meet the fire early water supply the most unfavorable floor and parts of fire water pressure and water requirements.
(2)
高位消防水箱的儲(chǔ)水量應(yīng)該與實(shí)際的消防火災(zāi)中的供水需求總量來(lái)生產(chǎn)制作,建議消防水箱儲(chǔ)水量應(yīng)滿足60s消防系統(tǒng)所需2支水箱和4只噴頭的用水量
。
high fire water tank of water storage should be with the actual fire water demand to production, suggested that the fire water storage tank water should meet the 60s fire system required 2 tank and four nozzle of water.
(3)消防水箱設(shè)置高度應(yīng)滿足火災(zāi)初期消防系統(tǒng)不利點(diǎn)所需要的低工作壓力
。
the fire water tank setting height should meet the minimum working pressure of the fire protection system at the most unfavorable point.
(4)設(shè)置常高壓給水系統(tǒng)并能不利點(diǎn)消火栓和自動(dòng)噴水滅火系統(tǒng)等的水量和水壓的建筑物,如果出現(xiàn)此種情況可以不設(shè)消防水箱
。
set constant high pressure water supply system and to ensure the most unfavorable point fire hydrant and sprinkler system water and water pressure building, if such a situation can not set fire water tank.